Silence THIN-WALL ETWW

Silence THIN WALL ETWW, water-fed wall-mounted fan coil unit, “THINW-V-Auto” version, featuring a modern design and reduced depth (130 mm), ideal for any space, perfectly blending in with the furniture.
It is available in different sizes depending on the requested heat output, it can be installed on the wall and connected to “two-pipe” systems with hot or cold water.

Category:

Description

The “THINW-V-AUTO” version with on-board thermostat is able to create and maintain the ideal conditions for well-being all year round, in any residential space thanks to the SMART TOUCH command with touchpad display on the front, and infrared remote control (supplied standard) to control the ambient temperature, fan speed, and operating mode.
The fan coil unit is equipped with the latest DC-INVERTER technology with high-performance permanent magnet fan motor, with speed and power regulation through the PWM electronic device, with noise reduction and power savings of up to 50%.

The unit is complete with air filter, condensate drain filter, and jig for wall fixing.

 

Model Total Cooling Capacity [kW] med (min – m… Heating Capacity Prated,h [kW] med (min… Air flow rate [m³/h] med (min – max) Q.ty per pack. Code
ETWW 240 DQ 
0,80 (0,48 – 1,07)
0,94 (0,53 – 1,27)
155 (84 – 228)
1 pcs
07523525
ETWW 260 DQ 
1,03 (0,58 – 1,65)
1,26 (0,66 – 1,80)
229 (124 – 331)
1 pcs
07523535
ETWW 280 DQ 
1,75 (0,91 – 2,31)
1,98 (0,96 – 2,60)
283 (138 – 440)
1 pcs
07523545
ETWW 240 SQ 
0,80 (0,48 – 1,07)
0,94 (0,53 – 1,27)
155 (84 – 228)
1 pcs
07523625
ETWW 260 SQ 
1,03 (0,58 – 1,65)
1,26 (0,66 – 1,80)
229 (124 – 331)
1 pcs
07523635
ETWW 280 SQ 
1,75 (0,91 – 2,31)
1,98 (0,96 – 2,60)
283 (138 – 440)
1 pcs
07523645

 

Cooling performance under the following standard nominal conditions:
– internal Air temperature = 27 (19) °C
– Water temperature = 7/12 °C
Heating performance under the following standard nominal conditions:
– internal Air temperature = 20 °C
– Water temperature = 45/40 °C
Information requirements for fancoils according to Regulation EU 2016/2281.
Performance according to EN 1397:2016, EN 16583:2015 standards.
Power supply: 230 Vac/1 ph/50 Hz.
Standard water connection on the left side.